Line connection and line-side power components3.7 Line filtersBooksize Power UnitsManual, (GH2), 04/2014, 6SL3097-4AC00-0BP6 813.7.6 Basic Line Filter for Smart Line Modules3.7.6.1 DescriptionBasic Line Filters for Smart Line Modules are designed to attenuate conducted interferenceemissions in accordance with the specifications contained in the relevant EMC legislation.They are mainly effective in the frequency range from 150 kHz to 30 MHz; this is the rangerelevant to ensure compliance with the appropriate standard.Basic Line Filters for Smart Line Modules can achieve the interference voltage categorieslisted below, when used in conjunction with the associated line reactors and an EMC-compliant design (see Chapter Possible line reactor and line filter combinations (Page 136)).● EN 61800-3 category C2 up to a total cable length 1) of 350 m (shielded) for 5 kW to55 kW components● EN 61800-3 category C3 up to a total cable length 1) of 350 m (shielded) for 5 kW to55 kW componentsBasic Line Filters are only suitable for direct connection to TN systems. An isolatingtransformer is required for other power systems.1) Maximum total cable length = Σ motor cables, line supply conductor from line filter to Line1) ModuleArtisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com