Line Modules Booksize4.8 Smart Line Modules with internal air coolingBooksize Power UnitsManual, (GH2), 04/2014, 6SL3097-4AC00-0BP6 2814.8.3.3 X21 EP terminalsSmart Line Modules 5 kW and 10 kWTable 4- 66 X21 EP terminal for Smart Line Modules 5 kW and 10 kWTerminal Designation Technical data1 DO: Ready Feedback signal: Smart Line Module readyThe signal switches to high level when the followingconditions have been met:• Electronics power supply (X24) OK• DC link is precharged• Pulses enabled (X21.3/4)• No overtemperature• No overcurrent2 DO: Prewarning DO: PrewarningHigh = no prewarningLow = prewarning• Overtemperature warning threshold/I 2 t5 kWprewarning: 64 °C, overtemperature threshold: 69 °C10 kWprewarning: 68 °C, overtemperature threshold: 73 °C• No regenerative feedback capability due to a line fault[only monitored when feedback is activated (seeterminal X22.2)]3 EP +24 V (pulse enable) Voltage 24 V DCCurrent consumption: 10 mAIsolated input4 EP M (Enable Pulses)Type: Screw terminal 1 (Page 755)Max. cross-section that can be connected: 1.5 mm2Terminals X21.1 and X21.2NoteWiring to a digital input of the Control UnitOutput terminal X21.1 must be wired to a digital input on the CU. The drives supplied withpower from the Smart Line Module have to use this signal as a ready signal. This ensuresthat a pulse enable can only be issued for the drives (motor or generator operation) when theinfeed is ready.If interconnection with a digital input on the CU is not possible, the signal must be evaluatedby a higher-level control system instead. It is not permissible that the control system sets thedrives to ready until the infeed "Ready" signal is present.Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com