Motor Modules Booksize6.4 Motor Modules with cold plateBooksize Power UnitsManual, (GH2), 04/2014, 6SL3097-4AC00-0BP6 4496.4.4 Meaning of LEDsTable 6- 36 Meaning of the LEDs on the Motor ModuleStatus Description, cause RemedyRDY DC LINKOff Off The electronics power supply is missing or outside thepermissible tolerance range.–Green -- The component is ready for operation. Cyclic DRIVE-CLiQ communication is taking place.–Orange The component is ready for operation. Cyclic DRIVE-CLiQ communication is taking place.The DC link voltage is present.–Red The component is ready for operation. Cyclic DRIVE-CLiQ communication is taking place.The DC link voltage is outside the permissible tolerancerange.Check the line supplyvoltage.Orange Orange DRIVE-CLiQ communication is being established. –Red -- At least one fault is present in this component.Note:The LED is driven irrespective of the correspondingmessages being reconfigured.Resolve and acknowledgethe fault.Green/red (0.5Hz)-- Firmware is being downloaded. –Green/red (2Hz)-- Firmware download has been completed. The systemwaits for POWER ON.Carry out a POWER ON.Green/orangeorred/orange-- Component recognition via LED is activated 1) .Note:Both options depend on the LED status whencomponent recognition is activated.–1) See SINAMICS S120/S150 List Manual for the parameters to activate the recognition of components via LEDWARNINGDanger of death when live parts of the DC link are touchedIrrespective of the state of the LED "DC LINK", hazardous DC link voltages can be present.This means the touching of live parts can result in death or serious injury.• Observe the warning information on the component.Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com