Line Modules Booksize Compact5.1 Smart Line Modules Booksize CompactBooksize Power Units352 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6Terminals X21.1 and X21.2 - temperature sensor connectionWARNINGDanger to life due to electric shock in the event of voltage flashovers on the temperaturesensor cableVoltage flashovers in the signal electronics can occur in motors without safe electricalseparation of the temperature sensors.• Only use temperature sensors that fully comply with the specifications of the safetyisolation.• If safe electrical separation cannot be guaranteed (for linear motors or third-partymotors, for example), use a Sensor Module External (SME120 or SME125) or TerminalModule TM120.NOTICERisk of the motor overheating due to an incorrectly connected KTY temperature sensorA KTY temperature sensor connected with incorrect polarity cannot detect if the motoroverheats.• Always connect the KTY sensor with the correct polarity.Terminals X21.3 and X21.4WARNINGDanger to life when live parts are touched when terminals X21.3 and X21.4 are connectedFor operation, the 24 V DC voltage must be connected to terminal X21.3 and ground toterminal X21.4.Pulse cancellation is activated if the power supply is disconnected. Regenerative feedbackis deactivated and the bypass relay drops out. If the Line Module is not disconnected fromthe line supply when the EP terminal is de-energized, for example, because a line contactoris not installed, then the DC link remains charged.Death or serious injury can result when live parts are touched.• Neutralize the voltage in the DC link.NOTICEDamage to the drive electronics when switching the line contactor under loadWhen switching the line contactor (type according to the recommended selection) underload, then the contacts will be subject to premature wear. This can cause the contactor tomalfunction, with subsequent damage to the drive electronics.• Use a leading opening auxiliary contact or use a Voltage Sensing Module (VSM10).• If this is not possible, then avoid switching the line contactor under load.Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com