Panasonic Electric Works Fire & Security Technology Europe ABMEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x9526.5.2 Algorithm setting via menu H4/U5NOTE! Algorithm setting via menu H4/U5 is only valid for the"British Standard Marine Application" convention.The alarm algorithm can be set (changed) via menu H4/U5 for thefollowing detectors:3304 in NORMAL mode3308 / 3309 in NORMAL mode3316 in NORMAL mode (the "Decision algorithm" is not possible touse)No alternative algorithm can be used.No values (offset, level, etc.) can be set via menu H4/U5 (i.e. thesevalues have to be set via Win512).The "Short name" (set in Win512) can be < 5 characters.When scrolling the message "Please Wait….." might be shown for " asecond" and "No more sensors found in the system" (before the lowestand after the highest possible technical number in the system).NOTE! If an algorithm is set (changed) via menu H4/U5, the sitespecific data (SSD) in the c.i.e. is not equal to the SSD filedownloaded from Win512, i.e. a back up is required to update theSSD file (xxxxxx.512).If an algorithm is set (changed) via menu H4/U5, the information inmenu H5/A4 will be changed from "Downloaded: xxxx" to "Modifiedby CU: xxxx".Follow the instructions for 3304, 3308 / 3309 and 3316 respectively: