Panasonic Electric Works Fire & Security Technology Europe ABMEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x7121.1 Boot menuThe Boot menu should be used by authorised personnel only!NOTE! Vital data can be erased via this menu.The Boot menu is opened as follows:Perform a reset / restart:• Power off / power onor• Jumper JP4 on the main boardThe following text messages will be show in the alphanumericdisplay:Checking program memory......And after that:Booting......When the text "Booting……" appears, press "Access" and 0.1 sec.later also press "1" and the Boot menu will be shown:1:Reset, 2:Clear mem, 4:Read AD, 5:MSClock, 6:Checksum, 7:Cursor, 8:TextsPress "1" to perform a reset / restart (i.e. you will also leave the Bootmenu).Press "2" to open the Clear memory menu, see below.The other alternatives are for R & D use only!!The Clear memory menu:1 = SSD, 2 = SSW, 3 = SysInfo, 4 = Echeloninfo, 5 = TextsPress "1" to clear the SSD memory. 70Press "2" to clear the SSW memory.The other alternatives are for R & D use only!!"Erasing SSD" and "Erasing SSW" respectively will be shown andthen will the Clear memory menu be shown again.Press "Return" go back to the Boot menu.NOTE! After clearing the SSW, perform a "Power off / power on"reset / restart directly.70 Can also be done in Win512, EBL512 settings dialog box, "Clear SSD".