Panasonic Electric Works Fire & Security Technology Europe ABMEW00748 Rev: 1 Operating Instructions Fire alarm system EBL512 V2.3.x217 Access levelsThe control unit has six access levels for different kind of users.Access level 0 Door closed Anybody Scroll / browse throughthe queued alarmsAccess level 1 Open door(key is required)Fire brigade personnel Fire alarm handlingAccess level 2 Access code forlevel 2 (or 3 or 4)is requiredBuilding occupier Installation handling,monthly tests,disablements, etc.Access level 3 Access code forlevel 3 (or 4) isrequiredService personnel Service, maintenanceAccess level 4 Access code forlevel 4 isrequiredService /commissioningengineerService, commissioningthe system, etc.Access level 5 Access code forlevel 5 isrequiredService /commissioningengineerPC (Win512) connectionto EBL512.The access codes can be changed. To change a code you have toknow the valid code or use a code for a higher access level.7.1 Access level 0With the door closed, anybody has access to the push button "Alarmsqueued" (P1) to scroll / browse through the queued alarms.7.2 Access level 1After the door has been opened (LED "Door open" is lit), the user /fire brigade personnel has access to the push buttons / keypad to:(P2) Silence the buzzer in the c.i.e.(P3) Silence the alarm devices (sounders) in the system.(P4) Reset fire alarm(s).(P5) Evacuate (i.e. turn on the sounders). 18(P7) Paper feed (when built-in printer is available).(P8) Get access (after logon) to level 2-4, i.e. menus/functions in thesystem.18 Only valid in the "British Standard", Hungarian and Ukrainianconventions. In "Chinese" convention this button is used for "LED test". In"Polish" (CNBOP) convention this button can be used for "AlertAnnunciation Acknowledge". In "Australian" convention this button is usedto disable all zones "in alarm".