Panasonic Eco Solutions Nordic ABMEW01603 Rev: - EBL512 G3 version 2.0.x, Daily user's manual85.1 Zone or Zone / Address (B1)Up to 512 whole zones can be disabled via menu B1. Normally allalarm points within the zone will be disabled except the addressablemanual call points.Up to 200 alarm points (Zone / Address) can be disabled via menu B1.Disabled Zones and/or Zone / Addresses can also be Re-enabled viamenu B1.Cont. from , page 7.B1 Zone or Zone / Address Press ( ).DisableNOTE! To Re-enable, see ➓ below.By default is Zone 000 selected. Press the Soft key "Change typeof disablement" to toggle between:Zone 000Zone 000 address 00. Use the keypad to type the Zone or Zone / Address. Press ( ). If "Automatically re-enablement" shall be used, press ( and ) tohighlight Yes , accept the suggested time or use the keypad to typeanother time (hh:mm). Press ( ).A successful disablement is indicated by a beep and a "√". It will also beshown in the Re-enable list.A not successful disablement is indicated by another beep and a "X".Re-enable➓ Press the Soft key " ⇥ " to toggle between:DisableRe-enable list.Press ( ) to highlight the Zone or Zone / Address that shall be Re-enabled.⓫ Press ( ). A successful Re-enablement is indicated by a beep and itwill also disappear from the Re-enable list.⓬ To leave a menu press ESC.To leave the menu system press the Soft key "Escape menu".Escapemenu