38Cycle time of control output 2 (Cooling-side)(Setting range: 1 to 150 seconds) (Option: Available for DUAL output only)[Description]• By this parameter is set, the cycle time of control output 2.• While input is within the proportional band, outputchanges between ON and OFF in cycles. These cyclesare called cycle time.[Setting example] Setting the cooling-side cycle time from 30 seconds to 20 secondsOutput: ONCycletimeCycletimePress and hold theSEL key for three seconds.will be displayed on the PV display.Press the key to display .Press theSEL key once.The current setting ( ) flashes on the SV display.Press the or key to display .Press theSEL key once. will stop flashing and will be registered for . After that, thecontroller will operate with the cooling-side cycle time being 20 seconds.If you want to display the operation status, press and hold theSEL key for two seconds.Operating procedureDisplay1.2.3.4.5.6.For contact output:The higher the frequency of output is, the more precisethe control becomes. However a high frequency of out-put may shorten the life of the contacts and the device tobe controlled. Be sure to adjust the proportional cyclesconsidering controllability and the life of the device andthe contacts.Typical: 30 seconds• Do not set this parameter to "0".www. .com information@itm.com1.800.561.8187