62Fig.6-1 ACC and DEC timeWhen the reference frequency is equal to the maximum frequency,The actualacceleration and deceleration time will be equal to actual setting.When the reference frequency is less than the maximum frequency,the actualacceleration and deceleration time will be less than actual setting.The actual acceleration (deceleration) time=setting ACC/DEC time* reference frequency/maximum frequency.Inverter have 4 groups of ACC/DEC time1st group:F0.11、F0.12;2nd group:F8.00、F8.01;3rd group:F8.02、F8.03;4th group:F8.04、F8.05。By multifunction digital input terminal of the ACC/DEC time choose terminalcombination to choose ACC/DEC time.Code Name Setting RangeF0.13 Running direction selection 0~2【0】0:Runs at the default direction. the inverter runs in the forward direction.1:Runs at the opposite direction, the inverter runs in the reverse direction. This effectequals to the shifting the rotation direction by adjusting either two of the motor wires.Note: If the parameters are restored,the running direction will be back to itsoriginal status.It is careful to use to system debugging after is forbidden to changethe motor to occasion.