Document 50934 Rev B 5/15/00 PN 50934:B40The reporting structure for the Ademco Contact ID format is as follows:SSSS 18 QXYZ GG CCCwhereSSSS = Four digit Subscriber ID (addresses 17 - 20 and43 - 46)18 = Identifies transmission as Contact ID to thereceiver at the Central StationQ = Event Qualifier1 = New Event2 = New RestoreXYZ = Event code (shown in Tables 3-4 and 3-7)GG = Group number or Loop numberCCC = Device or Zone numberFor general reports (alarm, trouble and supervisory), the GG and CCC fieldsare transmitted as 00 and 000 unless changes to addresses 64-65 and 66-68are made.64 - 65 = Loop number (GG), (factory default is 00)66 - 68 = Device/Zone number (CCC) for General Alarm,Fault or Supervisory messages (factory default is 000).A typical printout of alarm and trouble reports in the Ademco Contact IDReporting Structure follows:Time Date SSSS QXYZ GG CCCC411:28 03/25 11 7777 E110 00 C000 - general alarm11:28 03/25 11 7777 E111 00 C046 - alarm SD4611:28 03/25 11 7777 E300 00 C000 - general trouble11:28 03/25 11 7777 E380 00 C046 - trouble SD4611:28 03/25 11 7777 R110 00 C000 - general alarm restore11:28 03/25 11 7777 R111 00 C046 - alarm SD46 restore11:28 03/25 11 7777 R300 00 C000 - general trbl restore11:28 03/25 11 7777 R380 00 C046 - trouble SD46 restoreTable 5-3: Ademco Contact ID Reporting StructureNotes:1) In the sample report, SD46 refers to smoke detector at address 46 oron zone 46.2) 18, which is used in the reporting structure to identify the transmissionas Contact ID, is not printed out in the alarm and trouble report.3) Q, which is the Event Qualifier for the reporting structure, is printed outin the report as an E for New Event or R for New Restore.4) CCCC, the first C is not transmitted by the ADT-UDACT but is printedby the Central Station Receiver printer output.Rcvr/Line ID