• Not allowed: no automatic initiation is allowed• When the synchronization fails, the automatic initiation is carried out when theauto wait time elapses and the reclosing is prevented due to a failure during thesynchronism check• When the circuit breaker does not close, the automatic initiation is carried outif the circuit breaker does not close within the wait close time after issuing thereclose command• Both: the automatic initiation is allowed when synchronization fails or thecircuit breaker does not close.The Auto init parameter defines which INIT_X lines are activatedin the auto-initiation. The default value for this parameter is "0",which means that no auto-initiation is selected.A070871 V1 ENFigure 381: Example of an auto-initiation sequence with synchronization failurein the first shot and circuit breaker closing failure in the second shotIn the first shot, the synchronization condition is not fulfilled (SYNC is FALSE).When the auto wait timer elapses, the sequence continues to the second shot.During the second reclosing, the synchronization condition is fulfilled and the closecommand is given to the circuit breaker after the second reclose time has elapsed.After the second shot, the circuit breaker fails to close when the wait close time haselapsed. The third shot is started and a new close command is given after the thirdreclose time has elapsed. The circuit breaker closes normally and the reclaim timestarts. When the reclaim time has elapsed, the sequence is concluded successful.9.4.4.3 Shot pointer controllerThe execution of a reclose sequence is controlled by a shot pointer. It can beadjusted with the SHOT_PTR monitored data.The shot pointer starts from an initial value "1" and determines according to thesettings whether or not a certain shot is allowed to be initiated. After every shot,Section 9 1YHT530004D05 DControl functions702 615 seriesTechnical Manual