Table 368:PDNSPTOC Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation Off / OnReset delay time 0...60000 ms 1 20 Reset delay timeMin phase current 0.05...0.30 xIn 0.01 0.10 Minimum phase current4.4.2.8 Monitored dataTable 369:PDNSPTOC Monitored dataName Type Values (Range) Unit DescriptionSTART_DUR FLOAT32 0.00...100.00 % Ratio of start time /operate timeRATIO_I2_I1 FLOAT32 0.00...999.99 % Measured current ratioI2 / I1PDNSPTOC Enum 1=on2=blocked3=test4=test/blocked5=offStatus4.4.2.9 Technical dataTable 370:PDNSPTOC Technical dataCharacteristic ValueOperation accuracy Depending on the frequency of the currentmeasured: fn ±2 Hz±2% of the set valueStart time < 70 msReset time < 40 msReset ratio Typical 0.96Retardation time < 35 msOperate time accuracy in definite time mode ±1.0% of the set value or ±20 msSuppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…4.4.3 Phase reversal protection PREVPTOC4.4.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPhase reversal protection PREVPTOC I2>> 46RSection 4 1YHT530004D05 DProtection functions456 615 seriesTechnical Manual