Name Type DescriptionOKPOS BOOLEAN Apparatus position is okOPEN_ENAD BOOLEAN Opening is enabled based on the input statusCLOSE_ENAD BOOLEAN Closing is enabled based on the input statusTable 593:ESXSWI Output signalsName Type DescriptionSELECTED BOOLEAN Object selectedEXE_OP BOOLEAN Executes the command for open directionEXE_CL BOOLEAN Executes the command for close directionOPENPOS BOOLEAN Apparatus open positionCLOSEPOS BOOLEAN Apparatus closed positionOKPOS BOOLEAN Apparatus position is okOPEN_ENAD BOOLEAN Opening is enabled based on the input statusCLOSE_ENAD BOOLEAN Closing is enabled based on the input status9.1.7 SettingsTable 594:CBXCBR Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation mode on/offSelect timeout 10000...300000 ms 10000 60000 Select timeout in msPulse length 10...60000 ms 1 100 Open and close pulse lengthOperation counter 0...10000 0 Breaker operation cyclesControl model 0=status-only1=direct-with-normal-security4=sbo-with-enhanced-security4=sbo-with-enhanced-securitySelect control modelAdaptive pulse 0=False1=True1=True Stop in right positionEvent delay 0...10000 ms 1 100 Event delay of the intermediate positionOperation timeout 10...60000 ms 500 Timeout for negative terminationTable 595:DCXSWI Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation mode on/offSelect timeout 10000...300000 ms 10000 60000 Select timeout in msPulse length 10...60000 ms 1 100 Open and close pulse lengthOperation counter 0...10000 0 Breaker operation cyclesTable continues on next pageSection 9 1YHT530004D05 DControl functions674 615 seriesTechnical Manual