PREMIER AD INSTALLATION MANUAL. Software:PANEL:R1107 & LOOP:R1062Approved Document No: GLT.MAN-105A PAGE 32Issue : 2.02 Authorised: GH Date: 16/07/200717. PANEL SPECIFICATIONS17.1 ENCLOSURE SPECIFICATIONSDESCRIPTION VALUEENCLOSURE SIZE 480 x 395 x 100 mmTOP CABLE ENTRIES 20 x 19mm DIA GROMMETED ENTRIESBOTTOM CABLE ENTRIES 10 x 19mm KNOCKOUT ENTRIESREAR CABLE ENTRIES 2 SNAP OUTS, 60 x 20mm17.2 ELECTRICAL SPECIFICATIONSELECTRICAL DESCRIPTION VALUEMAINS VOLTAGE 230V AC +/- 10% @ 50/60 HzBATTERY VOLTAGE 24V DC (2 X 12V SLA BATTERY)SYSTEM VOLTAGE 24V DC NOMINAL (18 – 32 V)SYSTEM VOLTAGE RIPPLE 2V PK-PK MAXCHARGER SIZE UP TO 7AH in 24 HoursZONE VOLTAGE 24V DC NOMINAL (+9 volt data)SOUNDER ALARM OUTPUTS 4 x 250mA @ 24V DC (Nominal)AUXILIARY FAULT OUTPUT 1 x RELAY SELV (1A MAX)AUXILIARY FIRE OUTPUT 1 x RELAY SELV (1A MAX)NUMBER OF LOOPS 2 LOOPSMAXIMUM NUMBER OF ZONES 16 ZONESMAXIMUM LOOP CAPACITY 126 DEVICES PER LOOPMAXIMUM ZONE CAPACITY 16 DEVICES PER ZONEMAXIMUM LOOP RESISTANCE 25 ohmsMAXIMUM LOOP CAPACITANCE 0.3μFMAXIMUM VOLTAGE PICKUP ALLOWED 50mVREMOTE SOUNDER ACTIVATION VIA N/O CONTACTSSOUNDER END OF LINE DEVICE 10 K RESISTORCHARGER VOLTAGE 28.3V @ 22-24 oC (NO BATTERY CONNECTED)LOOP SHORT CIRCUIT PROTECTION 750mACHARGER SHORT CIRCUIT PROTECTION Batteries less than 20VTOTAL CHARGER OUTPUT 1.5 Amp