PREMIER AD INSTALLATION MANUAL. Software:PANEL:R1107 & LOOP:R1062Approved Document No: GLT.MAN-105A PAGE 19Issue : 2.02 Authorised: GH Date: 16/07/2007caps lock as necessary.10. Press enter when the label has been entered.11. To skip many addresses, or to change loop, it ispossible to select the next loop and address to edit.Press button 1 or 2 to select the new loop. The Panelwill then prompt for the address. Type the address andpress enter. The panel will now jump to this address.The sounder symbol in the top right hand corner shows that this detector might havean “associated sounder base” connected. The panel will send the “activate basesounder” command to this address in the event of an alarm. See Sounder section &Sounder base setup for further information.12. When all devices have been entered, press Cancel to exit the message editingscreen, and cancel again to exit the menu and to return to normal.The panel is now configured and ready for operation.12.2 CONFIGURING THE SOUNDER BASESOn the Premier AD, all detectors are treated as if they have a sounder base duringthe initial configuration. If a loop contains a large number of detectors, and a smallnumber of sounder bases, then the sounders might take a long time (between 4 & 8seconds) to start.If this scenario exists, it is possible to speed up operation as shown below. (Note: ifevery detector has a sounder base, or if most of the detectors have a sounder basethis “speed up operation” will have little or no effect.1. Press enter, NEXT, followed by 369 to enterConfiguration Menu 2. Select option 5 to edit device status.Select a detector that does NOT have a sounder baseattached.2. Press the Disablement SELECT button. The soundersymbol turns off to show that this detector no longer hasan associated sounder. (Pressing select again willcontinue to toggle the sounder on & off.)3. Repeat for all detectors that do not have an associated sounder base fitted.12.3 SETTING TIME AND DATETo set the time & date, enter Configuration Menu 2 and select Configure System (6).The System Menu is now displayed. Select option 1 to set time & date. Enter theDay, Month, Year, Hour & Minutes as prompted, and press enter to save, or Cancelat any time to exit.12.4 SETTING A CUSTOM BANNEROn the Premier AD, the default screen shows Fire alarm Panel to EN54. But this canbe changed to any 2 lines of 20 Characters that are required. In the System Menu,type NaMe (Caps lock,N,Caps lock,a,Caps lock,M,Caps lock,e). Then type the firstline of text, followed by enter, then the second line of text, followed by enter. Thismessage will now be the screen when the panel is running normally.OpticalAnalog: 25 NormalFl 3 Bedroom 303Zone:01 Lp:1 Ad:016OpticalAnalog: 25 NormalFl 3 Bedroom 303Zone:01 Lp:1 Ad:016OpticalAnalog: 25 NormalFl 3 Bedroom 303Zone:01 Lp:1 Ad:016Enter Loop AddressLoop: 1Address: 000