H3 Multi-Function Analog Input SettingsH3-ooSetting Function LCD Display Description Page4 Output voltage bias Voltage Bias 10 V = E1-05 (motor rated voltage) –5 Accel/decel time gain Acc/Dec Change 10 V = 100% –6 DC Injection Brakingcurrent DC Brake Current 10 V = Drive rated current –7 Overtorque/undertorquedetection level Torque Det Level 10 V = Drive rated current (V/f)10 V = Motor rated torque (OLV/PM) –8 Stall Prevention levelduring run Stall Prev Level 10 V = Drive rated current –9 Output frequency lowerlimit level Ref Lower Limit 10 V = E1-04 (maximum output frequency) –B PI feedback PI Feedback1 10 V = 100% 171C PI setpoint PI Set Point 10 V = 100% 171D Frequency bias Freq Ref Bias 2 10 V = E1-04 (maximum output frequency) 171E Motor temperature (PTCinput) Motor PTC 10 V = 100% –F Through mode Not Used Set this value when using the terminal in the pass-through mode. –16 Differential PI feedback PI Feedback 2 10 V = 100% –25 Secondary PI Setpoint PI2 Setpoint 10 V = S3-02 (maximum output frequency) –26 Secondary PI Feedback PI2 Feedback 10 V = S3-02 (maximum output frequency) –u H4: Analog OutputsNo.(Addr.Hex) Name LCD Display Description Values PageH4-01(41D)Multi-Function AnalogOutput Terminal FMMonitor Selection Term FM FuncSelSelects the data to be output through multi-function analogoutput terminal FM.Set the desired monitor parameter to the digits available inUo-oo.For example, enter “103” for U1-03.Default: 102Range: 000 to655 –H4-02(41E) Multi-Function AnalogOutput Terminal FMGain Terminal FM GainSets the signal level at terminal FM that is equal to 100% of theselected monitor value. Default: 100.0%Min.: -999.9Max.: 999.9 –H4-03(41F) Multi-Function AnalogOutput Terminal FMBias Terminal FM BiasSets the signal level at terminal FM that is equal to 0% of theselected monitor value. Default: 0.0%Min.: -999.9Max.: 999.9 –H4-04(420)Multi-Function AnalogOutput Terminal AMMonitor Selection Terminal AM SelSelects the data to be output through multi-function analogoutput terminal AM.Set the desired monitor parameter to the digits available inUo-oo.For example, enter “103” for U1-03.Default: 103Range: 000 to655 –H4-05(421) Multi-Function AnalogOutput Terminal AMGain Terminal AM GainSets the signal level at terminal AM that is equal to 100% ofthe selected monitor value. Default: 50.0%Min.: -999.9Max.: 999.9 –H4-06(422) Multi-Function AnalogOutput Terminal AMBias Terminal AM BiasSets the signal level at terminal AM that is equal to 0% of theselected monitor value. Default: 0.0%Min.: -999.9Max.: 999.9 –H4-07(423)Multi-Function AnalogOutput Terminal FMSignal Level SelectionLevel Select10: 0 to 10 Vdc1: -10 to 10 Vdc2: 4-20 mA0: 0 to 10 V1: -10 V to 10 V2: 4 to 20 mA Default: 0Range: 0 to 2 –H4-08(424)Multi-Function AnalogOutput Terminal AMSignal Level SelectionAO Level Select20: 0 to 10 Vdc1: -10 to 10 Vdc2: 4 to 20 mA0: 0 to 10 V1: -10 V to 10 V2: 4 to 20 mA Default: 0Range: 0 to 2 –B.7 H Parameters: Multi-Function Terminals296 YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual