A.1 Power Ratingsu Three-Phase 600 V Class Drive Models 5A0003 to 5A0032Table A.1 Power Ratings (Three-Phase 600 V Class)Item SpecificationDrive Models 5A0003 5A0004 5A0006 5A0009 5A0011 5A0017 5A0022 5A0027 5A0032Maximum Applicable Motor Capacity(HP) <1> 2 3 5 7.5 10 15 20 25 30InputInput Current (A) <2> 3.6 5.1 8.3 12 16 23 31 38 45Rated VoltageRated Frequency Three-phase 500 to 600 Vac 50/60 HzAllowable VoltageFluctuation -10 (-15) to +10%Allowable FrequencyFluctuation ±5%Input Power (kVA) 4.1 5.8 9.5 14 18 26 35 43 51OutputRated Output Capacity(kVA) <3> <4> 2.7 3.9 6.1 9 11 17 22 27 32Rated Output Current(A) <4> 2.7 3.9 6.1 9 11 17 22 27 32Overload Tolerance 110% of rated output for 60 s140% of rated output for 0.5 sCarrier Frequency User adjustable between 1 and 12.5 kHzMaximum OutputVoltage (V) Three-phase 500 to 600 Vac (proportional to input voltage)Maximum OutputFrequency (Hz) 240 Hz<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater thanthe motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiringconnections, and power supply impedance.<3> Rated motor capacity is calculated with a rated output voltage of 575 V.<4> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.A.1 Power Ratings258 YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual