53 z vacon using macro mode and getting a quick startTel. +358 (0)201 2121 • Fax +358 (0)201 21220566.3 Macro Mode Applications and Included ParametersThe tables below list the different applications and the Level 1 parameters included in the macro for thatapplication. The Factory Application macro is the core package (listed in Table 17); the other macrosinclude the Factory Application macro parameters as well as the ones listed in their respective tables(Tables 18, 19, 20, 21, and 22). The macro mode applications are as follows:• Factory Application (Table 17)• Fan Application (Table 18)• Fan with PI Application (Table 19)• Pump Application (Table 20)• Pump with PI Application (Table 21)• Vector Application (Table 22)Para. # Parameter Name Default See Page001 Model Number Read-only 60010 Last Fault Read-only 60102 Output Freq Read-only 61103 Output Voltage Read-only 61104 Output Current Read-only 61105 Drive Load Read-only 61106 Load Torque Read-only 61107 Drive Temp Read-only 61111 DC Bus Voltage Read-only 62201 Input Mode Local Only 62202 Rev Enable Forward 63301 Min Frequency 0.0 Hz 67302 Max Frequency 60.0 Hz 67303 Preset Freq 1 50 Hz 67402 Accel Time 1 5.0 sec 68403 Decel Time 1 5.0 sec 68502 Voltage Boost 0.0% 72610 Timed OL Select In Duty 60sec 78700 Vmet Config Freq Out 79705 Relay 1 Select Drv Fault 80706 Relay 2 Select Drive Rdy 80Table 17:Factory Application MacroPara. # Parameter Name Default See Page203 Stop Key Remote Coast 63204 Ref Select Vin1 63205 Vin1 Config 0-10 V 64206 Vin1 Offset 0.00% 64207 Vin1 Span 100.00% 64406 DC Inject Config DC at Start 69501 V/Hz Select Fan Fixed 71504 Skip Freq Band 0.2 Hz 72505 Skip Freq 1 0.0 Hz 72Table 18:Fan Application Macro(Core Factory Application from Table 17, plus the following parameters)