summary of vacon 50x parameters vacon z 11424-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com12304 Preset Freq 2 Min Freq–Max Freq 10.0 Hz 67305 Preset Freq 3 Min Freq–Max Freq 20.0 Hz 67306 Preset Freq 4 Min Freq–Max Freq 30.0 Hz 67307 Preset Freq 5 Min Freq–Max Freq 40.0 Hz 67308 Preset Freq 6 Min Freq–Max Freq 50.0 Hz 67309 Cut-Off Freq 0.0–5.0 Hz 0.0 Hz 67401 Ramp Select text string(Size 0–4):ART-DI(Size 5):S-Curve67402 Accel Time 1 0.1–3200.0 sec 5.0 sec 68403 Decel Time 1 0.1–3200.0 sec 5.0 sec 68404 Accel Time 2 0.1–3200.0 sec 3.0 sec 68405 Decel Time 2 0.1–3200.0 sec 3.0 sec 69406 DC Inject Config text string DC at Stop 69407 DC Inject Time 0.0–5.0 sec 0.2 sec 69408 DC Inject Level 0.0–100.0% 50.0% 69409 DC Inj Freq 0.0–20.0 Hz 0.0 Hz 70410 DB Config text string Internal 70414 S Ramp Rounding 1–100% 25% 70490 App Macro text string Factory 50491 Seq Appl text string Disabled 50492 SIO Visible text string No 50501 V/Hz Select text string Linear Fxd 71502 Voltage Boost 0.0–50% 1.0% 72503 V/Hz Knee Freq 25.0–400.0 Hz 60.0 Hz 72504 Skip Freq Band 0.2–20.0 Hz 0.2 Hz 72505 Skip Freq 1 Min Freq–Max Freq 0.0 Hz 72506 Skip Freq 2 Min Freq–Max Freq 0.0 Hz 72507 Skip Freq 3 Min Freq–Max Freq 0.0 Hz 72508 Skip Freq 4 Min Freq–Max Freq 0.0 Hz 72509 Rated Mtr Volt 100V–690V Model Dependent 73510 Rated Mtr FLA 50%–200% of ND Rat-ing ND Rating 73511 Rated Mtr RPM 0–24000 rpm 1750 rpm 73512 Midpoint Freq 0.0 Hz–V/Hz KneeFreq 60.0 Hz 73513 Midpoint Volt 0.0–100.0% 100.0% 73514 Motor RS 0.0–655.35 Ohm Model Dependent 73515 Power Factor 0.50–1.00 0.80 73516 Slip Comp Enable text string No 74517 Single Phase text string No 74519 Find Mtr Data Not Active/Motor RS Not Active 74520 Filter FStator 1–100 ms 8 ms 74521 Start Field En Yes/No No 74522 Filter Time Slip 10–1000 ms 100 ms 75523 Id Percent 0–200% Read-only 75524 Iq Percent 0–200% Read-only 75No. Parameter Name Options Default User Setting See Page