10.12.2 SETPOINTSP3.12.2.1 KEYPAD SETPOINT 1 (ID 167)Use this parameter to set the setpoint value of the PID controller when the setpoint source is'Keypad SP'.The value of this parameter is given in the selected process unit.P3.12.2.2 KEYPAD SETPOINT 2 (ID 168)Use this parameter to set the setpoint value of the PID controller when the setpoint source is'Keypad SP'.The value of this parameter is given in the selected process unit.P3.12.2.3 SETPOINT RAMP TIME (ID 1068)Use this parameter to set the rising and falling ramp times for the setpoint changes.Ramp time is the time that is necessary for the setpoint value to change from minimum tomaximum. If the value of this parameter is set to 0, no ramps are used.P3.12.2.4 SETPOINT SOURCE 1 SELECTION (ID 332)Use this parameter to select the source of the PID setpoint signal.P3.12.2.5 SETPOINT 1 MINIMUM (ID 1069)Use this parameter to set the minimum value of the setpoint signal.P3.12.2.6 SETPOINT 1 MAXIMUM (ID 1070)Use this parameter to set the maximum value of the setpoint signal.P3.12.2.7 SLEEP FREQUENCY LIMIT 1 (ID 1016)Use this parameter to set the limit below which the output frequency of the drive must stayfor a set time before the drive goes to the sleep state.See the description of parameter P3.12.2.10.P3.12.2.8 SLEEP DELAY 1 (ID 1017)Use this parameter to set the minimum duration that the output frequency of the drive muststay below the set limit before the drive goes to the sleep state.See the description of parameter P3.12.2.10.P3.12.2.9 WAKE-UP LEVEL 1 (ID 1018)Use this parameter to set the level at which the drive wakes up from the sleep state.See the description of parameter P3.12.2.10.VACON · 168 PARAMETER DESCRIPTIONS10 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205