10 PARAMETER DESCRIPTIONSIn this chapter, you can find data on the most special parameters of the application. For mostparameters of the Vacon 100 application, a basic description is sufficient. You can find thesebasic descriptions in the parameter tables of Chapter 5 Parameters menu. If other data isnecessary, your distributor will help you.10.1 MOTOR SETTINGS10.1.1 MOTOR NAMEPLATE PARAMETERSP3.1.1.1 MOTOR NOMINAL VOLTAGE (ID 110)Find the value Un on the nameplate of the motor.Find out whether the motor connection is Delta or Star.P3.1.1.2 MOTOR NOMINAL FREQUENCY (ID 111)Find the value fn on the nameplate of the motor.P3.1.1.3 MOTOR NOMINAL SPEED (ID 112)Find the value nn on the nameplate of the motor.P3.1.1.4 MOTOR NOMINAL CURRENT (ID 113)Find the value In on the nameplate of the motor.P3.1.1.5 MOTOR COS PHI (ID 120)Find the value on the nameplate of the motor.P3.1.1.6 MOTOR NOMINAL POWER (ID 116)Find the value In on the nameplate of the motor.P3.1.1.7 MOTOR CURRENT LIMIT (ID 107)Use this parameter to set the maximum motor current from the AC drive.The range of values for the parameter is different for each enclosure size of the drive.When the current limit is active, the drive output frequency is decreases.NOTE!The Motor Current Limit is not an overcurrent trip limit.P3.1.1.8 MOTOR TYPE (ID 650)Use this parameter to set the type of motor in your process.VACON · 112 PARAMETER DESCRIPTIONS10 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205