– 6 –• Refrigerant (R410A)This air conditioner adopts a HFC type refrigerant (R410A) which does not deplete the ozone layer.1. Safety Caution Concerned to Refrigerant (R410A)The pressure of R410A is high 1.6 times of that of the previous refrigerant (R22).Accompanied with change of refrigerant, the refrigerating oil has been also changed.Therefore, be sure that water, dust, the previous refrigerant or the previous refrigerating oil is not mixed intothe refrigerating cycle of the air conditioner with refrigerant (R410A) installation work or service work.If an incorrect work or incorrect service is performed, there is a possibility of a serious accident.Use the tools and materials exclusive to R410A to ensure a safe work.2. Cautions on Installation/Service1) Do not mix other refrigerant or refrigerating oil.For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of theprevious refrigerant in order to prevent mixture of them.2) As the use pressure of the refrigerant (R410A) is high, use material thickness of the pipe and tools whichare specified for R410A.3) In the installation time, use clean pipe materials and work with great attention so that water and others donot mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.Use clean pipes.Be sure to braze with flowing nitrogen gas. (Never use any other gas except for nitrogen.)4) For the ground protection, use a vacuum pump for air purge.5) R410A refrigerant is azeotropic mixture type refrigerant.Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of therefrigerant changes and then characteristics of the air conditioner change.)3. Pipe MaterialsFor the refrigerant pipes, copper pipe and joints are mainly used.It is necessary to select the most appropriate pipes to conform to the standard.Use clean material in which impurities adhere inside of pipe or joint is minimal.1) Copper pipeThe pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipewithout seam” and one with bonded oil amount 0.0001 lbs / 32’ 10” (40mg / 10m) or less.Also do not use crushed, deformed, discolored (especially inside) pipes.(Impurities cause clogging of expansion valves and capillary tubes.)Use the flare nuts which are attached to the air conditioner unit.2) JointThe flare joint and socket joint are used for joints of the copper pipe.The joints are rarely used for installation of the air conditioner. However clear impurities when using them. PreviousNext |