8.4.146ES5 456-4UA12 DigitalOutput ModuleRated supply voltage L 115 to 230 V AC (47 to 63 Hz)Number of outputs 16, conditional short-circuit protection1)Isolation Yes, 2 groups of 8 outputsRange for supply voltage 88 to 264 V ACFusing 6.3 A fast, 1 fuse per 4 outputsOutput voltagefor logic 1for logic 0L- 1.5 V min.30 V max.Residual current at logic 0 5 mA max.Switching current (resistive, inductive load)ventilatednot ventilated40 mA to 2 A; 2) 6 A max. per 4 outputs40 mA to 1 A; 2) 4 A max. per 4 outputsSwitching current for lampsventilatednot ventilated40 mA to 2 A, 2.5 A max. per 4 outputs40 mA to 1 A, 2.5 A max. per 4 outputsContactor sizeper fuse groupfor all outputs0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC00 (Type 3TJ..) to 10 (Type 3TB54) at 115 V AC0 (Type 3TB40) to 8 (Type 3TB52) at 230 V AC00 (Type 3TJ..) to 4 (Type 3TB48) at 115 V ACMax. inrush current for≤ 3 ms≤ 20 ms≤ 50 ms25 A/group15 A/group13 A/groupPermissible line length 300 m max. unshieldedPower supplyDigital section from system bus 5 V, 100 mA typicalPower dissipation (rated operation) 39.0 WEnable input (F+/F-) Jumper in front connectorVoltage test to VDE 0160 Between two groups: 2000 V ACBetween group and ground point: 1500 V ACMechanical specificationsDimensions (W x H x D) 40 mm x 255 mm x 195 mmWeight Approx. 0.7 kg1) Protected by a fuse2) Contactors of Series 3TJ can only be operated at 115 V AC.8Specification Sheets for the ModulesSystem ManualC79000-B8576-C199-03 8 - 61