ELECTRICAL WORK27EnglishSpecification of the circuit breaker and power cableElectric CharacteristicsNorm. Ton Model Units Comp Fan motor MCA3) MOP 4)Hz Volts RLA1) #1 RLA1) #2 FLA2) #1 FLA2) #210 AG010KSVAFH 60 208/230 19.5 19.5 4 4 52 7015 AG015KSVAFH 60 208/230 27.5 27.5 4 4 70 9010 AG010KSVAJH 60 460 8.8 8.8 2 2 24 3015 AG015KSVAJH 60 460 16 16 2 2 40 501) Rated Load Ampere2) Full Load Ampere3) Minimum Circuit Ampere (A)4) Maximum Overcurrent Protective Device (A)NOTEŷRLA is based on AHRI 1230 Cooling Standard Condition.- Indoor temperature: 26.7°C (80°F) DB / 19.46°C (67°F) WB- Outdoor temperature: 35°C (95°F) DBŷVoltage tolerance is ± 10%.ŷMaximum allowable voltage between phases is 2%.ŷRefer to module combination table for independent unit's information.CAUTIONŷYou must install ELCB or MCCB + ELB- ELCB: Earth leakage circuit breaker- MCCB: Molded Case Circuit Breaker- ELB: Earth Leakage fuse BreakerŷDo not operate the outdoor unit before completing the refrigerant pipe work.ŷDo not disconnect or change the cable inside the product. It may cause damage to the product.ŷSpecification of the power cable is selected based on following installation condition; culvert installation/ambient temperature 30°C (86°F)/ single multi conductor cables. If the condition is different from the onesstated, please consult an electrical installation expert and reselect the power cable.- If the length of power cable exceeds 50 m (164.04 ft), reselect the power cable considering the voltagedrop.ŷUse a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outercover).ŷDo not use the power cable with the core wireexposed due to insulator damage occurred duringremoval of the sheath. When the core wire is exposed,it may cause fire.Example of exposed core wireInsulator(inner cover)Exposedwire coreSheath (outer cover)Electrical wiring work