Panasonic Eco Solutions Nordic ABMEW01623 Rev: - EBL128 Operating Instructions V2.0.x5718 FaultIn case of a fault condition, the following has happened / will happenin EBL128: The buzzer in EBL128 sounds steady (continuous). Output "R1" for routing equipment (Fault tx) is activated. Programmable output for general fault is activated Programmable output for general charge fault is activated ifit is a charge fault. LED "Fault tx activated" (L11) is turned ON. LED "General fault" (L7) is turned ON. LEDs "Fault / Disablements Alarm devices" (L13),"System fault" (L14) and/or "Fire brigade tx" (L15) might aswell be turned ON (depending on the type of fault). A fault message incl. date and time is shown in the display.NOTE! The way the date is presented could be different fordifferent languages.For an alarm point / zone also the "alarm text" will beshown.Example of a fault message for an alarm point (e.g. a detector):FAULT: No reply zz-aa Date: MM-DD Time: HH:MMPress "" to see more information:FAULT: No reply techn. address xxx User definable alarm text for zz-aaPress "" to see the zone-address: If more than one fault is activated, the text:"More faults" is added after the time. If a fault has been corrected before it has beenacknowledged, the "status" text: "Serviced" is addedafter the time.52 Fire alarm presentation has higher priority than the faultmessages. During fire alarm presentation the faults can beshown via the special fire alarm menu X2, see page 46.Faults are normally latched and have to be acknowledged, which isdone via menu H6 (see page 123). In menu (H6) can up to 200 faultsbe listed: Not serviced/corrected and not acknowledged faults Not serviced/corrected but acknowledged faults Serviced/corrected but not acknowledged faults52 In EBLWin, Fault latching can be selected (default) or not selected.Selected = each fault always have to be acknowledged. Not selected =corrected faults will automatically be removed from the fault list (menu H6).