Panasonic Eco Solutions Nordic ABMEW01623 Rev: - EBL128 Operating Instructions V2.0.x37When the outputs are disabled in the c.i.e. via menu H2/B4 it is notpossible to re-enable them from the FBF (via button "BrandfallSteuerungen ab").13.3 Indication "Brandfall Steuerungen ab"The indication "Brandfall Steuerungen ab" on "Feuerwehr-Bedienfeld" (FBF) is turned on if any of the three output typesControl, Fire ventilation and Extinguishing is disabled.13.4 Button "Akustische Signale ab"The button "Akustische Signale ab" on "Feuerwehr-Bedienfeld" (FBF)has the same function as the menu "Disable alarm devices" (H2/B9) inthe c.i.e.If pushed during fire alarm condition the button "Akustische Signaleab" will also silence the buzzer in the c.i.e.When the outputs are disabled from the FBF (via button "AkustischeSignale ab") it is not possible to re-enable them from the CIE.However, during fire alarm condition and if the outputs to fire alarmdevices (outputs C) have been disabled from the c.i.e. it is possible tore-enable them from the FBF.13.5 Indication "Akustische Signale ab"The indication "Akustische Signale ab" on "Feuerwehr-Bedienfeld"(FBF) is turned on when the outputs to alarm devices are disabled.13.5.1 Indication in button "Akustische Signale ab"(Switch "1" on the DIP switch in FBF (2003) shall be in position ON.)The LED in button "Akustische Signale ab" follow the indication"Akustische Signale ab" on "Feuerwehr-Bedienfeld" (FBF) i.e. LEDturned on means that the outputs to alarm devices are disabled.13.6 The buzzer in the c.i.e.Even if the outputs to alarm devices are disabled, the buzzer in thec.i.e. will re-sound in case of a new alarm. It is possible to silence thebuzzer by pressing the button "Akustische Signale ab" (outputs toalarm devices will be re-enabled) and immediately press the button"Akustische Signale ab" again (outputs to alarm devices will bedisabled again). In this case there is a risk that the alarm deviceswill sound for a short while.13.7 Button "ÜE ab"The button "ÜE ab" on "Feuerwehr-Bedienfeld" (FBF) will disable allthe outputs of type Routing equipment, nominated as output E in DINEN 54-1.