Lenovo System x PDU Technical Reference
.Input Line CordsThe following input line cords are for connecting the PDU to appropriate powercircuits. This may include for example, the wall or floor outlets to provide power tothe PDU. This PDU will need to be hardwired and has no plug. Refer to the HigherVoltage DC PDU Line cord and hard wiring section for additional information.PDU P/N Line CordP/NFeatureCode forBundle (PDU& Line Cord)Orderable Line cord description44T0966 Attached A580 Attached 90A DC line cord 90A@240-380VDC (4.3m) line cord hard wired (i.e. noplug)Note: RF-203P outlet refers to Rong Feng RF-203P DC outlet.Note: The high-voltage dc power cord that comes with the PDU must be connected toa properly wired and grounded high-voltage dc power source by a licensedelectrician. Refer to the HVDC Line cord and plug section for additional details.SpecificationsThe following table are specifications for the 44T0966 1U Higher Voltage DC PDU.Specifications Line cord PNInput Line Cord Type* 44T0966Type 90A/240V-380VDCPhase -Outlets types Six Rong Feng RF-203P DCPower Capacity** 21600WPower Limit per Outlet 15APower Limit per PDU 90AMonitoring/Switching No/NoU Space 1U or side pocketGrounding Screw Yes on back panel* For input line cord part numbers refer to the Input Line Cords section.96 |