Lenovo System x PDU Technical Reference
.Input Line CordThe following input line cord is for connecting the PDU to an appropriate powercircuits. This may include for example, the wall or floor outlets to provide power tothe PDU. Refer to the 0U PDU Attached line cord and plugs section for a picture ofthe line cord plug.PDU P/N FeatureCodeLine CordP/NLine Cord Description46M4137 5932 Attached Attached 3.0 meter line cord IEC-309 3P+N+G32A (32A / Phase) 380-415VAC Three PhaseWye 96A Total Circuit CapacitySpecificationsThe following table are specifications for the 46M4137 12 C13 / 12 C19 PDU.SpecificationsPDU Part Number 46M4137Feature Code 5932Input Line Cord Type* AttachedType 32A/380-415VACPhase Three PhaseOutlets: Twelve IEC C13, twelve IEC C19Power Capacity** 36480VA @ 380-415VACC19 limited to 16AC13 limited to 10APower Limit per Outlet C19 limited to 16AC13 limited to 10AGrouping Two C13 and two C19 outlets per breaker /Four C13 and four C19 outlets per phasePower Limit per Group 20A per breaker /32A per phasePower Limit per PDU 96APower Monitoring/Switching Yes/YesU Space 0UGrounding Screw Yes on front panel* For input line cord information refer to the Input Line Cord section.** For the purpose of this table, you can consider 1 VA = 1 Watt.149 |