.Circuit CapacitiesThe following table represents the derated values/Watt capacities for power circuitsrunning between 13A-63A@100V-415V for both single phase and three phaseelectrical circuits.Branch Circuit Rating Volt-ampere (VA)13A / 230V 1ph 2990VA15A / 230V 1ph 3450VA15A/ 240V 1ph 3600VA16A/ 220V 1ph 3520VA16A / 230V 1ph 3680VA16A / 240V 1ph 3840VA16A / 380V 3ph Y 6080VA / ph16A / 415V 3ph Y 6640VA / ph30A / 220V 1ph 6600VA32A / 220V 1ph 7040VA32A / 230V 1ph 7360VA32A / 240V 1ph 7680VA32A / 380V 3ph Y 12160VA / ph32A / 415V 3ph Y 13280VA / ph63A / 220V 1ph 13860VA63A/ 240V 1ph 15120VANote: the symbols represent the following:ph indicates phase (1 or 3),Δ indicates three phase delta,Y indicates three phase WYE,P indicates pole or hot conductor,N indicates neutral conductor, andG indicates ground conductor.15