LX and LT Low NOx Pool/Spa Heater Page 339.2 Service CodesThe LX and LT Low NOx controllers monitorseveral functions of the heater. In the event of amalfunction, the LX controller will display a servicecode on the left side of the LCD screen under the LXlogo (see Figure 34). The model LT displays thisinformation by lighting a set of indicator lights locatedon the front of the control panel (see Figure 35). Table11 lists the LX and LT Low NOx Heater ServiceCodes along with potential causes and remedies.Note: When the service codes marked with anasterisk (*) are displayed, the controls are stilloperable and the heater will operate normallywhen the displayed condition is remedied. Faultcodes without an asterisk (*) will shut down theheater and control panel, and a flashing"Service" icon will be displayed.9.3 Ignition Control LED Service CodesIn addition to the service codes shown in theprevious section, the ignition controller in both the LXand LT Low NOx model heaters has an LED light thatflashes to indicate various different faults. Table 9 liststhe LED codes and the corresponding fault description:Table 9. Ignition Control LED Fault CodesLED Code Fault DescriptionThe LED light is on Ignition Control Fault. Refer tocontinuously. qualified service personnel.LED single flash. Air flow fault.LED double flash. Flame exists when there is NO callfor heat. Refer to qualified servicepersonnel.LED triple flash. Ignition lockout (heater has cycledthree (3) times and locked out afterthe third try).Figure 34. LX Control PanelLAARSLAARSPOOL/OFF/SPABACKLIGHTRS SERVICEON LINE FOROPERATIONWITHCONTROLLERAquaLink RSTMLAARSPOOLOFFSPAHeatingSERVICE**SERVICE DIAGNOSTICS-SEE INSIDE FRONT DOORF°/C°SELECTTHERMOSTAT SETTINGSLow PressureHi Lim SwExt Sw 1Air Flo SwAGSExt Sw 2TempSensor188188 °F°C°F°CRS OnlineWaterTempThermostatSettingPool Spa F° C°Figure 35. LT Control PanelFigure 33. Flame view at high speedVIEW PORTBURNER FLAMEFigure 32. Flame view at low blower speedVIEW PORTBURNER FLAME