6-24 L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALMETERING CHAPTER 6: ACTUAL VALUES6 These actual values display without the corresponding time stamp as they become available per the recording ratesetting. Also, the recording post-filtering setting is applied to these values.6.4.10 PMU aggregatorACTUAL VALUES METERING PHASOR MEASURMENT UNIT PMU AGGREGATOR 1Actual values for the IEC 61850-90-5 PDU size are provided. These values allow you to know the approximate Ethernetframe size for the data streams from each aggregator. This can help to estimate network loading. The PDU size shown inthe displays does not include the Ethernet, UDP, or IP layers. PDU sizes approaching approximately 1500 bytes result infragmented data frames, causing increased network traffic.6.4.11 Transducer inputs and outputsACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xxActual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel IDand the bottom line as the value followed by the programmed units. PMU 1 V1:0.000 V 0.00° PMU 1 V2:0.000 V 0.00° PMU 1 V0:0.000 V 0.00°Range: Substituted with zero if delta-connected VTs PMU 1 IA:0.000 A 0.00° PMU 1 IB:0.000 A 0.00° PMU 1 IC:0.000 A 0.00° PMU 1 IG:0.000 A 0.00° PMU 1 I1:0.000 A 0.00° PMU 1 I2:0.000 A 0.00° PMU 1 I0:0.000 A 0.00° PMU 1 FREQUENCY:0.000 Hz PMU 1 df/dt:0.00 Hz/s PMU 1 CONFIG CHANGECOUNTER: 0Range: 0 to 65535 PMU AGGREGATOR 1 PMU AGGREGATOR 1PDU SIZE: 0 DCMA INPUT xx DCMA INPUT xx0.000 mA