5-158 L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALSYSTEM SETUP CHAPTER 5: SETTINGS5Figure 5-70: Disconnect switch control graphical front panel logic (sheet 3 of 3)5.5.7 FlexCurves5.5.7.1 SettingsSETTINGS SYSTEM SETUP FLEXCURVES FLEXCURE A(D)FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To entera custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using theMESSAGE up/down keys) for the required protection curve (A, B, C, or D). FLEXCURVE A FLEXCURVE A TIME AT0.00 xPKP: 0 msRange: 0 to 65535 ms in steps of 1 FLEXCURVE A TIME AT0.05 xPKP: 0 msRange: 0 to 65535 ms in steps of 1 FLEXCURVE A TIME AT20.00xPKP: 0 msRange: 0 to 65535 ms in steps of 1