2.3 Connecting Devices2.3.3 Connecting the RLY OUT Connector2-442.3.3 Connecting the RLY OUT ConnectorThe RLY OUT connector connects the status output terminal. It is an NO contact relay output.The RLY OUT connector is linked to the operation of the RDY indicator: The contacts closewhen the indicator lights, and they open when the indicator goes out.RLY OUT Connector SpecificationsThe operation of the RLY OUT connector is linked to the operation of the RDY indicator on theCPU Unit/CPU Module.RDY indicator lit: Circuit closedRDY indicator not lit: Circuit open Contact RatingsRLY OUT Connector Connection CableTo connect the RLY OUT connector, use a cable with a wire size of AWG28 to AWG14 (0.08 to2.0 mm 2 ) and a maximum outer diameter of 3.4 mm.The procedure to make the RLY OUT connector cable is the same as for the 24-VDC powersupply cable.When the RDY indicator is lit, the Controller is operating normally.It does not necessarily mean that the user programs are being executed.InputVoltage Current Capacity24 VDC 0.5 A (resistive load)0.25 A (inductive load)125 VAC 0.4 A (resistive load)0.2 A (inductive load)You can use the RLY connector only on the Rack to which the CPU Unit/CPU Module ismounted. On Racks without the CPU Unit/CPU Module, the power supply circuit is always open.NoteNote