Control connectionDS 400-2 04/2019 - V01 38Digital outputs (open emitter)5.3 Digital outputs (open emitter)DS-BAx-DPC/E-DS-400-digi-out-2Output voltageON level max. +24 V=OFF level <1 V=Output current nom 1 AOutput current max. 2 AReference voltage +24 (X1:4)Reference ground GNDE (X1:10)The logic outputs 1 to 3 are rated for 24 V and 1A (short-time: 2 A).Signal contact "Ready BTB/RDY" (Solid state relay)/ Ready BTB / RDYDS-BAx-DPC/E-DS-400-BTB-3Contact for max. 48 V/0.5 A(not short-circuit proof)Capacitive load max. 1 myFContact resistance max. 2 OhmThe contact is closedwhen the device is readyfor operation.State signal via seven-segment LED display.In case of failures the contact is open.Always install the BTB/RDY contact inthe safety circuit!Protect the BTB/RDY signal path bymeans of 0.5A!Ready for operation opens (red LED, open relay contact)in case of error messagesin case of under-voltage of the auxiliary voltage (<20 V)The message "under-voltage in the bus circuit" can be programmed. (Manual NDrive)Output Connection Function State ParameterBTB/RDY X1:1, X1:2 ready fixed/relayDOUT1 X1:13 Digital output 1 programmableDOUT2 X1:14 Digital output 2 programmableDOUT3 X1:17 Digital output 3 programmableDOUT4 Xx:Xx Digital output 4 programmable+ 24 V for logic and auxiliary voltageObserve the total current of all outputsGNDE logic ground_____________________DS-BAx-DPC/DS-400-lgoikspX1:13 DOUT1X1:14 DOUT2+24F_AUSx100nF24V/1ADSxx/BAxxX1:17 DOUT3Digital outputDigital output 1Digital output 2Digital output 3Digitaloutput(X1:N)(X1:O)(X1:S)(IP65)BTB/RDY Solid State RelaisF_BTB100nFX1:1X1:2DSxx/BAxxSafityCircuit