80Parameter Function / Title Bank Mask Adjustment Range Multiplier0133 STALL PROTECTIONENABLE 0 / 1 0040 0000: ON (0)0040: OFF (1)01340STALLPROTECTIONCURRENT LEVEL0 / 1 00FF 000A ∼ 00D7 (10 ∼ 215) 10135 UNDERVOLTAGE TRIPSELECTION 0 / 1 0080 0000: Trip disabled (0)0080: Trip (during run) (1)0136 UNDERVOLTAGE DETECTTIME 0 / 1 FFFF 0000 ∼ 03E8 (0.00 ∼ 10.00) 0.010137 LOW CURRENT DETECTSELECTION 0 / 1 0008 0000: Trip disabled (0)0008: Trip on detection (1)0138 LOW CURRENT DETECTLEVEL 0 / 1 00FF 0000 ∼ 0064 (0 ∼ 100) 10139 LOW CURRENTDETECTION TIME 0 / 1 00FF 0000 ∼ 00FF (0 ∼ 255) 10140 OUTPUT SHORT-CIRCUIT DETECTIONSELECT0 / 1 0003 0000: Standard motor (0)0001: High-speed motor (1)0002: Positioning use (standardmotor) (2)0003: Positioning use (high-speedmotor) (3)0141 OVERTORQUE TRIPSELECTION 0 / 1 0040 0000: Trip disabled (0)0040: Trip enabled (1)0142 OVERTORQUE TRIPLEVEL 0 / 1 00FF 0000 ∼ 00C8 (0 ∼ 200) 10143 FAULT TRIP EEPROMSAVE ENABLE 0 / 1 0002 0000: Data cleared when poweredOFF (0)0002: Data retained when poweredOFF (1)0144 COOLING FAN CONTROLSELECTION 0 / 1 0004 0000: Automatic (temperaturedetection) (0)0004: Always ON (1)0145 CUMULATIVE RUNTIMER ALARM SETTING 0 / 1 FFFF 0000 ∼ C34B (0.00 ∼ 999.90) 0.02