5813.6 Siemens FLNCurrently, the XLTR-200 supports Siemens application number 2750. Thisapplication acts as an FLN to Mitsubishi gateway.13.6.1 Ports• For this application, the FLN network must be connected to XLTR-200RS485 port A, and the Mitsubishi network must be connected to XLTR-200RS485 port B.• The FLN port (RS485 port A) requires no configuration other than the FLNnode address, which has a valid address range of 0 – 98. NOTE that thefactory default value is 99.• The baudrate and parity settings of the Mitsubishi port (RS485B port B)must be configured to match the serial settings of the connected ASD.NOTE that the factory default values for these settings are 9600 baud, noparity (8 data bits, 1 stop bit).• The ASD connected to RS485 port B must be configured as address #1 toallow the gateway to communicate with it (parameter 117 or 331 = 1).• Refer to section 12.3.2 for information about using the serial consoleinterface to configure XLTR-200 ports.