73Table 9: Input Terminal SelectionsSettingValueData(Hex) Function SettingValueData(Hex) Function0 10C8 R (reverse run) 28 04AF Binary bit #61 011C SS1 (preset speed selection) 29 08AF Binary bit #72 021C SS2 (preset speed selection) 30 10AF Binary bit #83 041C SS3 (preset speed selection) 31 20AF Binary bit #94 081C SS4 (preset speed selection) 32 40AF Binary bit #105 20C8 F (forward run) 33 04CE No effect6 201B RES (fault reset) 34 01C7 UP/DOWN frequency setting (UP)7 C0C9 ST (gate ON/OFF) 35 02C7 UP/DOWN frequency setting(DOWN)8 0CC8 JOG selection 36 04C7 UP/DOWN frequency clear9 081A Accel / decel #1/#2 selection 37 08C7 PUSH-type RUN key10 101B Emergency off 38 10C7 PUSH-type STOP key11 021B DC injection braking ON/OFF 39 02B9 No effect12 041B Fundamental parameterswitching (V/F #2)40 C0C8 Forward/reverse run selection13 011B Feedback control ON/OFF 41 20C7 RUN14 10CE Pattern run selection #1 42 30C9 Binary data write15 20CE Pattern run selection #2 43 0198 [LOCAL/REMOTE] key16 40CE Pattern run selection #3 44 0298 [MON] key17 80CE Pattern run selection #4 45 0498 [PRG] key18 02CE Pattern run continue signal 46 0898 [UP] key19 01CE Pattern run step trigger signal 47 1098 [DOWN] key20 0AC9 JOG forward run 48 2098 [READ/WRITE] key21 06C9 JOG reverse run 49 4098 [RUN] key22 10AE Binary bit #0 50 8098 [STOP/CLEAR] key23 20AE Binary bit #1 51 08CE Commercial power / inverterswitching signal24 40AE Binary bit #2 52 40C7 Reserved for option use25 80AE Binary bit #3 53 10CB RR frequency switching input26 01AF Binary bit #4 54 20CB IV frequency switching input27 02AF Binary bit #5Note: In order for binary bit #0 ∼ #10 (setting values 22 ∼ 32) and UP/DOWN frequency setting (setting values 34 &35) inputs to be valid, parameter FREQUENCY PRIORITY SELECTION #1 or FREQUENCY PRIORITYSELECTION #2 in GROUP:FREQUENCY SETTING PARAMETERS must be set to 5 (BIN (binary setting orUP/DOWN setting)).