– 7 –3 System control of Hot Water Module System able to be combinedThe High temperature Hot water module (H-HWM) is connectable to SHRM-e.In case of connecting at least one Hot water module in SHRM-e system, all of Flow Selector unit type should be Single port type Flow Selector unit (long piping model) or Multi port type Flow Selector unit.Model name of usable Flow Selector unit: RBM-Y1124FE, RBM-Y1804FE, RBM-Y2804FE, RBM-Y1801F6PE, RBM-Y1801F4PEThe Fresh Air intake type and Air to Air Heat Exchanger with DX Coil cannot be connected with the same refrigerant system.M-HWM: Mid temperature Hot water moduleH-HWM: High temperature Hot water moduleHWM: Mid temperature Hot water module and High temperature Hot water moduleNo. Item SHRM-e1 Indoor connectioncapacity(*1)Total Standard indoor unit + M-HWM + H-HWM 90 - 200% (*2) (*3)Standard indoor unit + M-HWM 90 - 135% (*2) (*3)AllowedcapacityStandard indoor unit 50 - 120% (*2)M-HWM 0 - 67.5% (*2) (*3)H-HWM 0 - 100% (*2) (*3)M-HWM + H-HWM 0 - 100% (*2) (*3)2 Maximum indoor unitquantityTotal Standard indoor unit + M-HWM + H-HWM 32Standard indoor unit + M-HWM 32AllowednumberStandard indoor unit 2 - 32M-HWM 0 - 14H-HWM 0 - 12M-HWM + H-HWM 0 - 143 Height differenceHeight difference between outdoorand indoor units H1 (*4)(Including HWM)H2 > 3 m Upper outdoor units 50 mLower outdoor units 30 mH2 ≤ 3 m Upper outdoor units 70 mLower outdoor units 30 mHeight difference between indoorunits(Including HWM)H2, H4, H5 (*4)Indoor - IndoorH2Upper outdoor units 40 mLower outdoor units 15 m (*6)HWM - HWMH4Upper outdoor units 40 mLower outdoor units 15 m (*6)Indoor - HWMH5Upper outdoor units 40 mLower outdoor units 15 m (*6)Height between outdoor units H3 5 mHeight difference between indoor units in group control by one Flow Selector unit H6 0.5 m13-EN 14-EN