Page 20 OPERATIONMANUAL OPERATIONPowerful springs. Do notplace your hands or anypart of your body insidethe circuit breaker whilethe indicators showCHARGED (yellow) or ON(red).To avoid damaging themechanism, do not closethe circuit breaker whenthe On-Off Indicator showsON (red).MANUAL CLOSING (Motor-Operated MU andML Types):1. Check to make sure that the On-Offindicator shows OFF (green).2. Attach the charging handle to the breaker if itis not already attached.3. If the closing spring status indicator showsDISCHARGED (white):Turn the charging handle clockwise 3 to 5times to charge the closing spring (Fig. 23).(Closing Spring Status Indicator changes toCHARGED, Yellow) When the handle isreleased, it returns to its normal position, anddo not attempt to turn again.If the closing spring status indicator showsCHARGED (yellow):Do not attempt to turn handle.Pushing the Green lever (Fig. 24) in thedirection of the arrow closes the circuitbreaker (On-Off indicator changes to ON)Fig. 23 Preparing to Manually ChargeBreakerFig. 24 Manually Closing BreakerWARNINGCAUTIONPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com