INSTALLATION Page 15MOUNTING DIRECTLY TO A SHELFThe shelf should be flat and level within ± 0.5mm (± 0.02 in.). If there are any noticeable gapsbetween the breaker and the shelf, fill them inusing flat washers as spacers.Check to make sure the breaker On-Off indicatorshows OFF (green), then mount it by followingthe steps below:1. Fasten the breaker onto steel angles or to aflate plate (Fig. 13). Use M8 hex head bolts(either 50 mm or 35 mm). The tighteningtorque should be 120-150 kgf-cm (9-11 ft-lb).2. Either mounting method shown in (Fig. 14)may be used.Fig. 13 Mounting Breaker to Flat Plate orAnglesFig. 14 Optional Hardware OrientationANGLEPANELM8 x 35MM OR M8 x 50MM BOLTPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com