5 - 18 5 - 18MELSEC-A5 PROGRAMMING(2) Initial setting by remote device station initialization procedureregistration function(a) Setting of target station numbersSet the station numbers to which initial setting will be made.Set the target station numbers to "1" and "4".(b) Selection of procedure registration (part 1)Make setting for the AJ65VBTCU-68ADI.Click Procedure registration of target station number "1".(c) Setting of procedure registration (part 1)Set the conditions and execution for the AJ65VBTCU-68ADI.When the initial data processing request flag (RX18) turns ON and Remotedevice station initialization procedure registration (SB0D) is set, thefollowing data are registered to the AJ65VBTCU-68ADI.Procedure Execution Condition in AJ65VBTCU-68ADI Execution DataA/D conversion enable/prohibit specification: Channel 1, 2: Enable(RWw0 :0003H)CH.1 to CH.4 input range setting : channel 1: 4 to 20mA: channel 2: user range setting(RWw1: 20H)Average processing specification : channel 1: sampling processing: Channel 2: Average processing, numberof times averaging(RWw3: 200H)CH. 2 average time, number of times setting: Channel 2: 16 times(RWw5: 10H)Initial data processing completion flag (RY18) is turned ON.Initial data processing request flag (RX18) turns ONInitial data processing request flag (RY19) is turned ON.Initial data processing request flag (RX18) turns OFF Initial data processing completion flag (RY18) is turned OFF.Initial data setting completion flag (RX19) turns ON Initial data setting request flag (RY19) is turned OFF.(d) Setting result (part 1)The following indicates the setting result of the AJ65VBTCU-68ADI.