3 - 15 3 - 15MELSEC-A3 SPECIFICATION3.6 Remote RegisterThe AJ65VBTCU-68ADVN/ADIN has a remote resister for data communication withthe master module. The remote register allocation and data structures are described.3.6.1 Remote register allocation(1) Remote register assignment for ver. 1 remote device station (ver. 1compatible slave station) settingTable 3.7 indicates the remote register assignment for ver. 1 remote devicestation (ver. 1 compatible slave station) setting.Table 3.7 Remote Register Assignment for Ver. 1 Remote Device Station (Ver. 1Compatible Slave Station) SettingCommunication direction Address Description Default value Reference sectionRWwm+0H A/D conversion enable/prohibit specification 0 Section 3.6.2RWwm+1H CH.1 to 4 input range setting 0RWwm+2H CH.5 to 8 input range setting 0 Section 3.6.3RWwm+3H Average processing specification 0 Section 3.6.4RWwm+4H CH.1 average time, number of times setting 0RWwm+5H CH.2 average time, number of times setting 0RWwm+6H CH.3 average time, number of times setting 0RWwm+7H CH.4 average time, number of times setting 0RWwm+8H CH.5 average time, number of times setting 0RWwm+9H CH.6 average time, number of times setting 0RWwm+AH CH.7 average time, number of times setting 0Master RemoteRWwm+BH CH.8 average time, number of times setting 0Section 3.6.5RWrn+0H CH.1 digital output value 0RWrn+1H CH.2 digital output value 0RWrn+2v CH.3 digital output value 0RWrn+3H CH.4 digital output value 0RWrn+4H CH.5 digital output value 0RWrn+5H CH.6 digital output value 0RWrn+6H CH.7 digital output value 0RWrn+7H CH.8 digital output value 0Section 3.6.6RWrn+8H Error code 0 Section 3.6.7Remote MasterRWrn+9HtoRWrn+BHReserved 0 ——m, n: Address allocated to the master module by the station number setting.POINTDo not read or write data from or to the reserved area of the remote register. If datais read or written, we cannot guarantee the functions of the AJ65VBTCU-68ADVN/ADIN.