Operation6.6 Communication according to PROFIdriveInverter chassis units230 Operating Instructions, 07/2016, A5E00331449AError values in parameter responsesTable 6- 15 Error values in parameter responsesErrorvalueMeaning Comment Additionalinfo0x00 Illegal parameter number. Access to a parameter that does not exist. –0x01 Parameter value cannot be changed. Modification access to a parameter value that cannot bechanged.Subindex0x02 Lower or upper value limit exceeded. Modification access with value outside value limits. Subindex0x03 Invalid subindex. Access to a subindex that does not exist. Subindex0x04 No array. Access with subindex to an unindexed parameter. –0x05 Wrong data type. Modification access with a value that does not match thedata type of the parameter.–0x06 Illegal set operation (only reset al-lowed)Modification access with a value not equal to 0 in a casewhere this is not allowed.Subindex0x07 Description element cannot bechangedModification access to a description element that cannotbe changed.Subindex0x09 No description data available Access to a description that does not exist (the parametervalue exists).–0x10 Read job will not be executed. The read request is refused because know-how protectionis active.–0x0B No parameter change rights. Modification access with no parameter change rights. –0x0F No text array exists Access to a text array that does not exist (the parametervalue exists).–0x11 Request cannot be executed due tooperating status.Access is temporarily not possible for unspecified reasons. –0x14 Illegal value. Modification access with a value that is within the limits butis illegal for other permanent reasons (parameter withdefined individual values).Subindex0x15 Response too long. The length of the present response exceeds the maximumtransfer length.–0x16 Illegal parameter address. Illegal or unsupported value for attribute, number of ele-ments, parameter number, subindex or a combination ofthese.–0x17 Illegal format. Write request: illegal or unsupported parameter data for-mat.–0x18 Number of values inconsistent. Write request: a mismatch exists between the number ofvalues in the parameter data and the number of elementsin the parameter address.–0x19 Drive object does not exist. You have attempted to access a drive object that does notexist.–0x20 Parameter text cannot be changed. – –0x21 0x21 Service not supported. Illegal or unknown request ID. –0x65 Parameter presently deactivated. You have tried to access a parameter that, although avail-able, does not currently perform a function (e.g., n controlset and access to a U/f control parameter).–