Chapter 4 - Data Communications Definitions© 2017 Siemens Protection Devices Limited Chapter 4 - Page 67 of 96Binary Input PointsStatic (Steady-State) Object Number: 1 (Packed Format)Change Event Object Number: 1 (w/o Time)Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)or 2 (Binary Input with status)Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)or 2 (Binary Input Change with Absolute Time)or 3 (Binary Input Change with Relative Time)PointIndex DescriptionDefault Change EventAssigned Class (1,2, 3 or none)Default VariationStatic Object 1Default VariationEvent Object 2397 25 CS In Progress 0,2 2 2398 25 SS In Progress 0,2 2 2399 25 COZ In Progress 0,2 2 2400 25 System Split LO 0,2 2 2401 60VTF-Bus 0,2 2 2411 Setting G1 selected 0,2 2 2412 Setting G2 selected 0,2 2 2413 Setting G3 selected 0,2 2 2414 Setting G4 selected 0,2 2 2415 Setting G5 selected 0,2 2 2416 Setting G6 selected 0,2 2 2417 Setting G7 selected 0,2 2 2418 Setting G8 selected 0,2 2 2420 79 AR In progress 0,2 2 2422 HotLine Working 0,2 2 2425 Inst Protection Out 0,2 2 2427 CB 1 0,2 2 2434 Man Override Sync 0,2 2 2435 79 Override Sync 0,2 2 2501 Virtual Input 1 0,2 2 2502 Virtual Input 2 0,2 2 2503 Virtual Input 3 0,2 2 2504 Virtual Input 4 0,2 2 2505 Virtual Input 5 0,2 2 2506 Virtual Input 6 0,2 2 2507 Virtual Input 7 0,2 2 2508 Virtual Input 8 0,2 2 2509 Virtual Input 9 0,2 2 2510 Virtual Input 10 0,2 2 2511 Virtual Input 11 0,2 2 2512 Virtual Input 12 0,2 2 2513 Virtual Input 13 0,2 2 2514 Virtual Input 14 0,2 2 2515 Virtual Input 15 0,2 2 2516 Virtual Input 16 0,2 2 2601 LED 1 0,2 2 2602 LED 2 0,2 2 2603 LED 3 0,2 2 2604 LED 4 0,2 2 2605 LED 5 0,2 2 2606 LED 6 0,2 2 2