7SR210 Settings GuideUnrestricted ©2018 Siemens Protection Devices Limited Page 55 of 613.8.2. Binary Output Config (Variants may differ)Description Range DefaultTrip ContactsThe Binary Outputs selected by this setting are classed as Tripcontacts. (When any of these BOs operate the Trip LED is lit,CB Fail is started, if enabled, & a Fault Record is stored)Combination of ( BO1, to B16) --------Hand Reset OutputsRelays selected, as Hand Reset will remain latched untilmanually reset from front panel or via communications link orby removing DC Supply. By default relays are Self Resettingand will reset when the driving signal is removed.Combination of ( 1, to 16) --------Min Operate Time 1Minimum operate time of output relay if set to self reset, if alsoset to be pulsed then this is the pulse width0, 0.01 ... 59, 60 0.1 s-Min Operate Time 8Minimum operate time of output relay 8 if set to self reset, ifalso set to be pulsed then this is the pulse width0, 0.01 ... 59, 60 0.1 sPick-up OutputsSelects which outputs can operate because a pickup conditionexistsCombination of ( 1 to 16) --------Pulsed OutputsSelects which outputs are pulsed. The pulse width is set bythe Min Operate Time setting for each outputCombination of ( 1 to 16) --------