Installation requirementsEnglish 11Ducting requirementsRecommended Use only for short-run installationWeather hoodtype4” (10.2 cm) 2.5” (6.4 cm)No. of 90°elbows Rigid Metallicflexible* Rigid Metallicflexible*0 80 ft. (24.4 m) 41 ft. (12.4 m) 74 ft. (22.6 m) 33 ft. (10.1 m)1 68 ft. (20.7 m) 37 ft. (11.2 m) 62 ft. (18.9 m) 29 ft. (8.8 m)2 57 ft. (17.4 m) 33 ft. (10.1 m) 51 ft. (15.5 m) 25 ft. (7.6 m)3 47 ft. (14.3 m) 29 ft. (8.8 m) 41 ft. (12.5 m) 21 ft. (6.5 m)NOTE* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.If you integrate the dryer’s vent system with an existing exhaust system, makesure:• The exhaust system meets all applicable local, state, and national regulations.• Not to use a flexible plastic duct.• To regularly check and clean all lint buildup from inside the existing ducts.• The duct is not kinked or crushed.• The exhaust hood damper opens and closes freely.Manometer measurementsThe static pressure in any exhaust system must not exceed 0.83 inches of water columnor be less than 0. Note that these values are measured with the dryer running with amanometer presented to the exhaust duct that connects to the dryer. The dryer tumblermust be empty and lint filter clean.DV7450M-03170Z-00_EN.indd 11 2017-01-25 11:24:17 |