Panasonic Electric Works Nordic ABMEW01091 Rev: 3 EBL128 Operating Instructions V1.1.x8525.4 Disable all control, extinguishing, venti-lation and alarm device outputs (H2/B4)Outputs programmed as type Control (general), type Fire ventilation,type Extinguishing system and type Alarm devices can for the typerespectively be disabled all at the same time. Disabled output meansthat even if the control expression (trigger condition) for the outputrespectively is fulfilled (true), the output will not be activated.Disabled outputs are shown in menu H4/U1.The outputs will be disabled until re-enabled again (via H2/B8).NOTE! This function for alarm devices is not the same as for pushbutton "Silence alarm devices" (P3), see chapter "Silence Alarmdevices", page 27. This function has higher priority than "Silencealarm devices".Action Text in display Comments"Access" According to chapter"Access", see page 78.Scroll to menu H2. Disable or re-enableACCEPT? H2"A" Disable zoneACCEPT? B1Scroll to menu B4. Disable all control, ventilation, extingor alarm device outputs ACCEPT? B4"A" Disable type: 0 0=Control 1=Ventilation2=Exting 3=Alarm devices ACCEPT?Press:"0"=control output"1"= ventilation output"2"= extinguishing output"3"=alarm device output.Press "A" to accept.LED "Disablements" (L8)will light up.If type 3 = alarm devicesare disabled also the LED"Fault / DisablementsAlarm devices" (L13) willlight up.Press 0, 1, 2 or 3"A"Disable all control, ventilation, extingor alarm device outputs ACCEPT? B4Scroll or press "Return" tomenu H2. Scroll or press"Return" to log off."Return" Disable or re-enableACCEPT? H2