Panasonic Electric Works Nordic ABMEW01091 Rev: 3 EBL128 Operating Instructions V1.1.x44Press "" (to see the next fault).16.2.1.3 Display disablements (X3)NOTE! Also zones in "Test mode" will be displayed via this menu.001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Display disablements ACCEPT? X3Press "A"001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Zone XX address XX disabledPress "" (to see the next disablement).NOTE! After all disablements will zones in "Test mode" bedisplayed.001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Zone in TEST MODE: 01 02 03 0416.2.1.4 Disable zone (X4)001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Disable zone ACCEPT? X4Press "A"001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Disable zone: 00 ACCEPT?Write a zone number (01 – 32) and press "A". If more zones are to bedisabled, repeat the procedure.16.2.1.5 Disable zone / address (X5)This function is useful e.g. for a manual call point not to continue togenerate alarms because of a broken glass.001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Disable zone / address ACCEPT? X5Press "A". E.g.:001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Disable zone: 00 Address: 00 ACCEPT?Write a zone-address and press "A". If more zone-addresses are to bedisabled, repeat the procedure.16.2.1.6 Re-enable zone (X6)001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01Re-enable zone ACCEPT? X6Press "A". E.g.: