Panasonic Electric Works Nordic ABMEW01090 Rev: 3 EBL128 Planning Instructions V1.1.x95Annunciation function. Only Analog photo electric smoke detector4301 and Analog multi detector 4300 can be used for AAF. If theAnalog multi detector 4300 is used, it must be programmed as type"Two addresses", so that only the "smoke part" of the detector can beused for AAF.Max. 50 AAF zones can be used.The AAF buzzer (e.g. Sounder base 3378) has to be programmed withthe output trigger condition "AAF zone alarm".13.11 Quiet alarmQuiet alarm is e.g. used in conjunction with the I/O Matrix board4582103, an application board for fan control and an I/O unit 3361 forfan control.NOTE! These units are available on the Australian market only.Smoke detectors, programmed for quiet alarm, can be used e.g. forcontrolling fans (stop / start depending on the type of fan).Indications and actions: In the c.i.e. display: Quiet alarm detector ZZ/AA and auser definable text message (alarm text) if programmed. LED:s "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.). Buzzer in the c.i.e. sounding (0.8 / 5 sec.). Programmable outputs for quiet alarm, e.g. 3361 outputscontrolling supply air fans and standard fans i.e. any outputwith a control expression containing trigger conditions "QuietAlarm Zone" or "Quiet Alarm Zone Address".Quiet alarms are non-latching, i.e. they will be automatically resetwhen the alarm point / zone is no longer above alarm level.NOTE! Quiet alarm can also be programmed for a 3361 unit "zoneline input". In such a case only non-latching detectors can be used.13.12 Fire alarm type A and Fire alarm type BNormally the c.i.e. relay output "R0" is used as an output for Routingequipment (Fire brigade tx).The output shall be programmed (via Win128) as type "Routingequipment" and have the trigger condition "Fire brigade tx". Theoutput will then be activated for fire alarm from any alarm point orzone line input.If the fire alarm routing equipment has provision for transmission ofseveral fire alarm signals and the alarm receiver has provision forreception of several fire alarm signals, a fire alarm type B will indicatethat only one detector is activated, which could be a nuisance alarm.103 See "I/O Matrix board 4582", page 22.